EasyManua.ls Logo

Belimo NMV-D2M - Enable OPERATION; Disable OPERATION; Status Information

Belimo NMV-D2M
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
4A1PC-T V2.1 NMV-D2M-EN 11-02-04.doc PM VAV - Subject to technical changes
VAV Module NMV-D2M
N-S3 Operation
Auto in control mode
Under nor mal circumsta nces the Au to mo de is ac ti ve. In this situa tion the VAV /
CAV controller is controlled via the reference input [w] or, in bus mode, via setpoint
issue.
The ‘Operation field is for checking the control functions either on-site or
on the manufacturer’s test rig.
N-S3.1 Enable ‘OPERATION
Pressing this button enables or disables operating step control of the
NMV-D2M.
The ‘OPERATIONbutton is disabled when LIVE TREND’ or ‘TEST’ are
active.
N-S3.2 Disable OPERATION
The preset operating step must be disabled after the Operation function
has been used!
If during active operating step control the communication conductor
between the PC-Tool and the VAV controller suffers open-circuit, the pre-
set operating step will remain stored in the NMV-D2M.
Reset (power-down) will return the NMV-D2M to Auto mode.
N-S3.3 Status information
Status line when ‘Operationis active:
- PC status: ‘Operation’ active
- NMV-D2M status: the preset operating step
N-S3.4 Local override control
In order to ensure active local override control these local commands are
given a higher priority.
e.g.: CAV air box withClose’ override control.
Active local override control when the NMV-D2M module is also issuing
an operating step is indicated by means of a red square symbol:
!
Note Disable operation
Before communication with the NMV-D2M is inter-
rupted the active mode of operation must be dis-
continued by disabling the ‘OPERATION’ function !
!
Override control / Operating steps
By appropriate connection of the reference input [w]
of the NMV-
D2M it is possible to select different
modes of operation.
See 4. NMV-D2M Product Information
Auto with the Tool connected
- Conventional mode: In this situation the VAV /
CAV controller is controlled via the reference input
[w].
- Bus mode: When there is active communica-
tion with an operating device, setpoint issue from
the higher level system (e.g. UK24LON) is inter-
rupted. Without direct setpoint issue from the Tool
the NMV-D2M is controlled from the reference
input [w] (0 V = V’min or, with a sensor connection,
according to the sensor value, 0...10 V).

Related product manuals