EasyManua.ls Logo

Bender ISOMETER iso415R - RS-485 Interface; Relay

Bender ISOMETER iso415R
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
iso415R-x_D00401_00_M_XXEN / 04.2021 15
ISOMETER® iso415R
3.2.1.2 RS-485 interface
B
A
B
A
B
A
B
A
max. 1 m
max. 1200 m
120 Ω
120 Ω
Specification
The RS-485 specification restricts the cable
length to 1200m and requires a daisy chain
connection.
A twisted-pair, shielded cable must be used as
bus cable. For example, cable type J-Y(St)Y
nx2x0.8 mm² is suitable. The shield must be
connected to PE at one end.
Termination
The bus cable must be terminated at both ends
with resistors (120 Ω, > 0.25 W). The terminat-
ing resistors are connected in parallel to the
terminals A and B.
i
If there are more than 16 bus devices, the
interface must be designed to be shock-
proof, because the maximum permissible
total leakage current of 0.5 mA is exceed-
ed.
3.2.1.3 Relay
The terminals 11,14,12 are relay outputs. The
following settings can be made via the Modbus
RTU interface:
i
Caution! High contact currents damage
the hard gold plating of the relay con-
tacts. Damaged contacts prevent the re-
lay from switching correctly at low con-
tact currents.
14
12
Function State Description
Relay mode NO principle |
NC principle
The relay mode can be adapted to the application:
N/C NC operation of the contacts 11-14-12. In fault-free condition,
the alarm relay is energised.
N/O NO operation of the contacts 11-14-12. In fault-free condition,
the alarm relay is de-energised.
Test on* | o This parameter determines whether the relay is actuated during a test
Main alarm on* | o The relay switches when the measured value falls below the response value of the main
alarm AL2
Prewarning on | o* The relay switches when the measured value falls below the response value of the prewarn-
ing AL1
Device error on* | o The relay switches if a device error exists
Connection fault
system
on* | o The relay switches when there is a system connection fault (L1, L2).
Connection fault earth on* | o The relay switches when there is a connection fault to earth (E, KE).
C
e
exceeded on* | o The relay switches when the permissible system leakage capacitance C
e
is exceeded.
* Factory setting

Other manuals for Bender ISOMETER iso415R

Related product manuals