Operation and setting
24
RCMA423_D00063_03_M_XXEN/03.2021
Parameter settings
An example is given here on how to change the alarm response value I1 (I
Δn1
).
It is presumed that the option overcurrent (HI) has been selected in the SEt/I
12 menu (factory setting). Proceed as follows:
1. Press the MENU/Enter key for more than 1.5 seconds. The flashing short
symbol AL appears on the display.
2. Confirm with Enter. The parameter response value > I2 flashes, in addi-
tion the associated overcurrent value > 30 mA appears.
3. Use the Down key to select the parameter response value I1. The para-
meter I1 flashes, in addition the associated percentage value for
prewarning 50 % of I2 appears.
4. Confirm with Enter. The current value for prewarning appears on the
flashing display.
5. Use the Up or Down key to set the appropriate prewarning value. Con-
firm with Enter. I1 flashes.
6. You can exit the menu by:
pressing the Enter key for more than 1.5 seconds to reach the next
higher level or
selecting the menu item ESC and confirming with Enter to reach the
next higher level.
The currently active segments are flashing! In the figures
below, the segments where device settings can be carried out
are highlighted by an oval. The menu mode can be reached
by pressing the MENU key for more than 1.5 seconds.

Table of Contents

Other manuals for Bender RCMA423

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender RCMA423 and is the answer not in the manual?

Bender RCMA423 Specifications

General IconGeneral
BrandBender
ModelRCMA423
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals