EasyManua.ls Logo

Bender RCMA423 - Technical Data and Settings; Factory Default Settings

Bender RCMA423
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data
33
RCMA423_D00063_03_M_XXEN/03.2021
6. Data
6.1 Factory setting
Response value
- overcurrent I1 (prewarning)
- overcurrent I2 (main alarm)
Hysteresis
Fault memory M
Operating mode K1/K2
Start-up delay
Response delay
Delay on release
Password
15 mA (50 % of I2)
30 mA
15 %
activated (on)
N/C operation (n.c.)
t = 0.5 s
t
on1
= 1 s
t
on2
= 0 s
t
off
= 1 s
0, deactivated (Off)

Table of Contents

Other manuals for Bender RCMA423

Related product manuals