Data
34
RCMA423_D00063_03_M_XXEN/03.2021
6.2 Error codes
Should, contrary to all expectations, a device error occur, error codes will ap-
pear on the display. Typical error codes are described below:
Error code Meaning:
E.01
Fault CT connection monitoring
Appropriate action: Check CT connection for short-circuit or
interruption. After eliminating the fault, the error code will be
automatically deleted.
E.02
Fault CT connection monitoring during manual self test.
Appropriate action: Check CT connection for short-circuit or
interruption. After eliminating the fault, the error code will be
automatically deleted.
E…
Appropriate action when error codes > 02 occur:
Appropriate action: Carry out a reset. Reset the device to fac-
tory setting. After eliminating the fault, the error code will be
automatically deleted. If the fault continues to exist, please con-
tact the Bender Service.