EasyManuals Logo

Bender RCMA423 User Manual

Bender RCMA423
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
Data
34
RCMA423_D00063_03_M_XXEN/03.2021
6.2 Error codes
Should, contrary to all expectations, a device error occur, error codes will ap-
pear on the display. Typical error codes are described below:
Error code Meaning:
E.01
Fault CT connection monitoring
Appropriate action: Check CT connection for short-circuit or
interruption. After eliminating the fault, the error code will be
automatically deleted.
E.02
Fault CT connection monitoring during manual self test.
Appropriate action: Check CT connection for short-circuit or
interruption. After eliminating the fault, the error code will be
automatically deleted.
E…
Appropriate action when error codes > 02 occur:
Appropriate action: Carry out a reset. Reset the device to fac-
tory setting. After eliminating the fault, the error code will be
automatically deleted. If the fault continues to exist, please con-
tact the Bender Service.

Table of Contents

Other manuals for Bender RCMA423

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender RCMA423 and is the answer not in the manual?

Bender RCMA423 Specifications

General IconGeneral
BrandBender
ModelRCMA423
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals