Data
35
RCMA423_D00063_03_M_XXEN/03.2021
6.3 Technical data
( )* = factory setting
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
RCMA423-D-1
Rated insulation voltage ................................................................................................................. 100 V
Overvoltage category/ pollution degree............................................................................................III/3
Rated impulse voltage ................................................................................................................... 2,5 kV
RCMA423-D-2
Rated insulation voltage ................................................................................................................ 250 V
Overvoltage category/ pollution degree............................................................................................III/3
Rated impulse voltage....................................................................................................................... 4 kV
Supply voltage
RCMA423-D-1
Supply voltage range U
s
.......................................................................... AC 24…60 V / DC 24…78 V
Operating range U
s
................................................................................. AC 16…72 V / DC 9.6…94 V
Frequency range U
s
..................................................................................................... DC, 42…460 Hz
RCMA423-D-2
Supply voltage range U
s
.......................................................................................... AC/DC 100…250 V
Operating range U
s
................................................................................................... AC/DC 70…300 V
Frequency range U
s
........................................................................................................... 42…460 Hz
Protective separation (reinforced insulation) between................... (A1, A2) - (k/l, T/R) - (11, 12, 14) - (21, 22, 24)
Voltage test according to IEC 61010-1 ............................................................................................................... 2.21 kV
Power consumption ......................................................................................................................................... ≤ 6.5 VA
Measuring circuit
External measuring current transformer ............................................................... CTUB101-CTBC20…210(P) series
Rated insulation voltage (measuring current transformer) ................................................................................. 800 V
Operating characteristic acc. to DIN EN 62020 and IEC 60755 ........................................................................... Type B
Rated frequency......................................................................................................................................... 0…2000 Hz