EasyManuals Logo

Bender RCMA423 User Manual

Bender RCMA423
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
Data
35
RCMA423_D00063_03_M_XXEN/03.2021
6.3 Technical data
( )* = factory setting
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
RCMA423-D-1
Rated insulation voltage ................................................................................................................. 100 V
Overvoltage category/ pollution degree............................................................................................III/3
Rated impulse voltage ................................................................................................................... 2,5 kV
RCMA423-D-2
Rated insulation voltage ................................................................................................................ 250 V
Overvoltage category/ pollution degree............................................................................................III/3
Rated impulse voltage....................................................................................................................... 4 kV
Supply voltage
RCMA423-D-1
Supply voltage range U
s
.......................................................................... AC 24…60 V / DC 24…78 V
Operating range U
s
................................................................................. AC 16…72 V / DC 9.6…94 V
Frequency range U
s
..................................................................................................... DC, 42…460 Hz
RCMA423-D-2
Supply voltage range U
s
.......................................................................................... AC/DC 100…250 V
Operating range U
s
................................................................................................... AC/DC 70…300 V
Frequency range U
s
........................................................................................................... 42…460 Hz
Protective separation (reinforced insulation) between................... (A1, A2) - (k/l, T/R) - (11, 12, 14) - (21, 22, 24)
Voltage test according to IEC 61010-1 ............................................................................................................... 2.21 kV
Power consumption ......................................................................................................................................... ≤ 6.5 VA
Measuring circuit
External measuring current transformer ............................................................... CTUB101-CTBC20…210(P) series
Rated insulation voltage (measuring current transformer) ................................................................................. 800 V
Operating characteristic acc. to DIN EN 62020 and IEC 60755 ........................................................................... Type B
Rated frequency......................................................................................................................................... 0…2000 Hz

Table of Contents

Other manuals for Bender RCMA423

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender RCMA423 and is the answer not in the manual?

Bender RCMA423 Specifications

General IconGeneral
BrandBender
ModelRCMA423
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals