Data
37
RCMA423_D00063_03_M_XXEN/03.2021
Switching elements
Number of switching elements ............................................................................................. 2 x 1 changeover contact
Operating principle .......................................................................... N/C operation / N/O operation (N/C operation)*
Electrical endurance, number of cycles................................................................................................................ 10000
Contact data acc. to IEC 60947-5-1
Utilisation category...............................................................AC-13..........AC-14..........DC-12..........DC-12....... DC-12
Rated operational voltage .................................................... 230 V ..........230 V ............ 24 V ..........110 V ........ 220 V
Rated operational voltage UL............................................... 200 V ..........200 V ............ 24 V ..........110 V ........ 200 V
Rated operational current..........................................................5 A...............3 A...............1 A........... 0.2 A......... 0.1 A
Minimum contact load (relay manufacturer's reference)....................................................................... 10 mA/5 V DC
Environment / EMC
EMC ............................................................................................................................................................. EN 61326-1
Ambient temperatures
Operating temperature .............................................................................................................. –25…+55 °C
Transport .................................................................................................................................... –25…+70 °C
Long-term storage .................................................................................................................... –25…+55 °C
Classification of climatic conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) ................................................ 3K23 (no condensation, no formation of ice)
Transport (IEC 60721-3-2) ........................................................................................................................ 2K11
Long-term storage (IEC 60721-3-1) ......................................................................................................... 1K22
Classification of mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) .............................................................................................................. 3M11
Transport (IEC 60721-3-2) ........................................................................................................................ 2M4
Long-term storage (IEC 60721-3-1) ...................................................................................................... 1M12
Option "W" data different from the standard version
Classification of climatic conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) ................................... 3K23 (condensation and formation of ice is possible)
Classification of mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) ............................................................................................................... 3M12

Table of Contents

Other manuals for Bender RCMA423

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender RCMA423 and is the answer not in the manual?

Bender RCMA423 Specifications

General IconGeneral
BrandBender
ModelRCMA423
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals