EasyManua.ls Logo

Bertec FIT - Site Preparation

Bertec FIT
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Bertec Corporation Instrumented Treadmill Manual 11
Site Preparation
In case of a oor installation, at least a 60 cm (2 ft) area on all sides of the treadmill should be clear and unobstructed for a proper
installation.
In case of a pit installation, pit length and width should be at least 120 cm (4 ft) larger [60 cm (2 ft) on each side] than the
dimensions of the treadmill (L x W). In case of suspended ooring these minimum dimensions apply to the units of the raised
oor that needs to be removable (to decide on the exact locations of the support columns for suspended ooring consult Bertec
Corporation for detailed dimensional drawings). For a ush tread surface, 6 mm (¼”) should be added to the height of the
treadmill (parameter H in Figures 7 and 8). As indicated previously, the oor (bottom of the pit) should be at within ±⅛". The
following table summarizes the required dimensions for the treadmill pit:
FIGURE 4: Required pit dimensions for instrumented treadmill
Parameter Dimensions
Minimum pit length, cm (in) L + 120 (L + 48)
Minimum pit width, cm (in) W + 120 (W + 48)
Pit depth, mm (in) H + 6 (H + 0.25) Tolerance: ±3 mm (±⅛")
Note that for systems with the optional incline module, extra space is needed between the treads and adjacent false ooring to
allow the extra rotational motion of the incline unit.
Incorporating a wire conduit into the pit construction is recommended for safety reasons to avoid tripping over the cables. The
recommended diameter is 10 cm (4”) for straight conduits and 13 cm (5”) for conduits with bends and turns. Since the standard
length of the cables running between the treadmill and the electronics control unit is 9 m, the cable conduit lengths should be
sized accordingly allowing for any amount of extra slack cable needed. A guide wire should be available in the conduit to run the
cables. Alternatively, the cables can be run under the false ooring. In case of oor installations, over-the-oor cable covers can
be used as a safety precaution.
The pit should be cleaned thoroughly after construction and should be free of any debris and dust. Cleaning with a vacuum
cleaner is strongly recommended, as dust particles will prevent the mounting plate epoxy to attach to the oor properly.
Installation