Transport, Installation and Connection
4-13
4.10.3 Handling of cable shielding KW5/KW6
Outer cable shield:
The outer cable shield is only on the unit
connected through the gland. At the
loose end of the cable just cut the outer shield.
Inner cable shield:
The inner cable shield cut short at both ends. This
screen has no function by the compact flame controller
and can cause a short circuit, if it is connected!