34
2. Test the Daikin system as described in the installation
manual for the outdoor unit
3. For all models:
1. Switch ON the power supply and/or plug in all con-
nected units.
2. Switch ON the air curtain using the control panel.
3. Initialise the control panel
4. For CITY W and CYV:
1. Check that the heat exchanger is connected correctly.
2. Check that the central heating system or the Daikin
system is switched on.
3. Feel whether the discharged air stream gets warm. This
may take some time.
4. Vent the heat exchanger, if necessary.
For CYQ:
Operate the unit using the Daikin control panel and check
the function:
1. Switch ON the system. The unit must start to dis-
charge air.
2. Set the operating mode to heating and set the tempera-
ture to Maximum. After a short time, the unit must
start to discharge warm air.
3. Set the operating mode only to fan. After a short time,
the unit must start to discharge cool air.
4. Switch OFF the system. After a short time, the unit
must switch itself OFF.
For CITY E:
1. Make sure heating is enabled in the control panel.
2. Feel whether the discharged air stream gets warm.
For CTY A:
Feel whether the unit discharges air.