INSTALLATION COMFORT AIR CURTAIN
20
2.7 Connecting the unit to the power supply
2.7.1 All models
Warning:
w Do not turn on the unit from the power
supply. Use the control panel.
Warning:
w The unit must be earthed (grounded).
Warning:
w Connect the unit in accordance with the
applicable local requirements.
2.7.2 Fuse ratings
Warning:
w Every unit must be separately fused in
accordance with the table below.
Fuse ratings
M
AXIMUM AMPERAGE ON
TYPE PLATE L1, L2 OR L3
MAXIMUM FUSE RATING A
<= 10 A 16 A
<= 15 A 20 A
<= 20 A 25 A
<= 25 A 35 A
<= 35 A 50 A
<= 50 A 63 A
<= 65 A 80 A
<= 80 A 100 A
<= 102 A 125 A
Note:
n Multiple units may only be served by a common fuse
if their total current consumption is less than 10 A.
See also:
1.3.4 Type plate 8