EasyManua.ls Logo

Binder KMF-240 - 9.4 Selecting between “set-point ramp” and “set-point step”; 9.5 Program entry as “set-point ramp” or as “set-point step”

Default Icon
99 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
KMF (E5.2) 06/2014 page 48/99
9.4 Selecting between set-point rampand set-point step
Set-points always refer to the start of a program section, i.e., at the beginning of each program section
the entered set-point is targeted. During program section operation, the temperature or humidity gradually
passes to the set-point entered for the next program section.
By appropriate planning of the program section timing, you can enter all kinds of temperature and humidi-
ty transitions:
Gradual temperature / humidity changes “set-point ramp”
The set-point changes its value gradually while proceeding from one program section to the next one
during the programmed section length. The actual temperature or humidity value (X) follows the con-
tinually moving set-point (W) at any time.
Program sections with constant temperature / humidity
The initial values of two subsequent program sections are identical; so the temperature or humidity
remains constant during the whole time of the first program section.
Sudden temperature / humidity changes “set-point step”
Steps are temperature or humidity changes (ramps) that occur during a very short interval. A section
with a different set-point follows two program sections with an identical set-point. If the duration of this
transitional program section is very short (minimum entry 1 sec), the temperature or humidity change
will proceed rapidly within the minimum amount of time.
Figure 15: Possible temperature or humidity transitions
The following chapter offers examples of programming a set-point rampand a set-point step”.
9.5 Program entry as set-point rampor as set-point step
In order to avoid incorrect programming, we recommend plotting both the temperature and humidity pro-
files (chart templates in chap. 9.11 and 9.12) and entering the values into a table (templates in chap 9.13
and 9.14).
The controller provides 8 operation lines (non-functional with standard unit) that can be activated or de-
activated for each program section.
01
02
03
04
05
06
07
08
09
W
t

Table of Contents

Related product manuals