KB-206-2 71
Emergency service – menu EMO:
Menu item Function
F2+F4⇒PAr⇒EMO⇒SME
Modbus: 16502
Enable operation without suction pressure transmitter
0 = operation mode deactivated
1 = operation mode activated
Ex-factory setting: 0 = manual operation deactivated
F2+F4⇒PAr⇒EMO⇒dME
Modbus: 16503
Enable manual operation without high pressure transmitter
0 = operation mode deactivated
1 = operation mode activated
Ex-factory setting: 0 = operation deactivated
F2+F4⇒PAr⇒EMO⇒AOE
Modbus: 16504
Enable substitute value for ambient temperature
0 = substitute value deactivated
1 = substitute value activated
Ex-factory setting: 0 = substitute value deactivated
F2+F4⇒PAr⇒EMO⇒AO
Modbus: 16505
Substitute value for ambient temperature
-200.0 – 200.0 °C
Ex-factory setting: 25.0 °C
F2+F4⇒PAr⇒EMO⇒COE
Modbus: 16506
Enable substitute value for cold store temperature
0 = substitute value deactivated
1 = substitute value activated
Ex-factory setting: 0 = substitute value deactivated
F2+F4⇒PAr⇒EMO⇒CO
Modbus: 16507
Substitute value for cold store temperature
-200.0 – 200.0 °C
Ex-factory setting: 25.0 °C
F2+F4⇒PAr⇒EMO⇒dOE
Modbus: 16508
Enable substitute value for discharge gas temperature
0 = substitute value deactivated
1 = substitute value activated
Ex-factory setting: 0 = substitute value deactivated
F2+F4⇒PAr⇒EMO⇒DO
Modbus: 16509
Substitute value for discharge gas temperature
-200.0 – 200.0 °C
Ex-factory setting: 100.0 °C
F2+F4⇒PAr⇒EMO⇒FPE
Modbus: 16416
Signal for condenser fans speed in case of a sensor error
0.0 – 100.0%
Ex-factory setting: 50.0%
The condensing unit includes emergency operation
modes and possibilities for manual intervention for the
case that faults are active on electronic or electrical
components. The continued use of the condensing unit
is possible with slight losses in functionality and/or per-
formance until a suitable spare part or a solution is
available. Emergency operation modes must not be
used for continuous operation of the condensing unit.
The user must have sufficient technical expertise to
make decisions regarding permissibility and impact of
the functions. Only one of the emergency operation
modes may be active at any given time.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bitzer ECOLITE LHL3E/2DES-2Y and is the answer not in the manual?

Bitzer ECOLITE LHL3E/2DES-2Y Specifications

General IconGeneral
BrandBitzer
ModelECOLITE LHL3E/2DES-2Y
CategoryHeat Pump
LanguageEnglish

Related product manuals