Monitoring of the application limits – menu ALr:
Menu item Function
F2+F4⇒PAr⇒EMO⇒dHA
Modbus: 16426
Maximum condensing pressure (software high pressure switch)
0.0 – 100.0 °C
Ex-factory setting: 62.0 °C
F2+F4⇒PAr⇒EMO⇒dHd
Modbus: 16427
Hysteresis at the max. condensing pressure (software high pressure switch)
0.0 – 10.0 K
Ex-factory setting: 5.0 K
F2+F4⇒PAr⇒EMO⇒SLA
Modbus: 16428
Minimum suction pressure (software low pressure switch)
-60.0 – 50.0 °C
Ex-factory setting: -45.0 °C
F2+F4⇒PAr⇒EMO⇒SLd
Modbus: 16429
Hysteresis at the min. suction pressure (software low pressure switch)
0.0 – 10.0 K
Ex-factory setting: 5.0 K
The ECOLITE controller monitors certain application
limits of the compressor or switches the compressor off
to protect it as soon as the application limits are ex-
ceeded.
When changing the refrigerant type (parameter Ert), the
ECOLITE controller sets the parameter dHA to the fol-
lowing presetting for the different refrigerants:
REF R404A R134a R407C R507A R407A R407F R450A R448A R513A R449A
dHA 62°C 70°C 55°C 62°C 60°C 60°C 70°C 60°C 70°C 60°C
When changing the refrigerant type (parameter Ert), the
ECOLITE controller sets the parameter SLA to the fol-
lowing presetting for the different refrigerants:
REF R404A R134a R407C R507A R407A R407F R450A R448A R513A R449A
SLA -45°C -25°C -25°C -45°C -40°C -40°C -25°C -40°C -25°C -40°C
If the cold store control is active, monitoring of the min-
imum and maximum overheating of the suction gas is
not possible and therefore deactivated.