74
Configuration Mode - Complete menu (FULL)
(1)In = nominal drive current
Code Name/Description Adjustment range Factory setting
FUn-
Function menu (continued)
CLI-
Current limitation menu
LC2
2
nd
current limitation commutation
nO
nO
L1H
L2H
L3H
L4H
L1L
L2L
L3L
L4L
Assignment
Function inactive.
L1H: LI1 active high
L2H: LI2 active high
L3H: LI3 active high
L4H: LI4 active high
L1L: LI1 active low
L2L: LI2 active low
L3L: LI3 active low
L4L: LI4 active low
If the assigned input is at 0, the first current limitation is active.
If the assigned input is at 1, the second current limitation is active.
See LI assignment information on page 45
CLI
Current limitation
0.25 to 1.5 In (1) 1.5 In
First current limitation.
CAUTION
RISK OF MOTOR DAMAGE
Check that the motor will withstand this current, particularly in the case of permanent magnet synchronous motors,
which are susceptible to demagnetization.
Failure to follow these instructions can result in equipment damage.
CL2
Current limitation 2
0.25 to 1.5 In (1) 1.5 In
Second current limitation
This function allows reduction of the drive current limit.
Visible only if 2
nd
current limitation commutation LC2 is not set to nO.
CAUTION
RISK OF MOTOR DAMAGE
Check that the motor will withstand this current, particularly in the case of permanent magnet synchronous motors,
which are susceptible to demagnetization.
Failure to follow these instructions can result in equipment damage.
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-

Related product manuals