BOGE FOCUS compressor control for piston compressors Page 35
FOCUS 1.10 Parameter overview
P031 After-running time 0 s...600 s USER
P032
In case of oil lubricated motors:
Monitoring of air temperature = Warning
0 = Fault,
1 = Warning
USER
P042 Suction pressure (booster pressure) 0...174 psi USER
P044 Message type Oil monitoring 1: Fault, 0: Warning USER
P050 Modbus address
0 for Master,
2...4 for additional compressors,
1...248 for other applications
USER
P051 Modbus baud rate 1200...115200 USER
P052 Modbus communication parameter
8Even1, 8None1, 8None2, 8Even2, 8Odd1 and
8Odd2
USER
P053 Modbus address (module)
0 for Master,
2...4 for additional compressors,
1...248 for (pure) control applications
USER
P054 Modbus baud rate (module) 1200...115200 USER
P055 Modbus communication parameter (module)
8Even1, 8None1, 8None2, 8Even2, 8Odd1 and
8Odd2
USER
P060 Contact type for compressed air treatment 0: Break contact, 1: Make contact USER
P061 Message type for compressed air treatment 1: Fault, 0: Warning USER
P063 External output release 0...2 USER
P064 Monitoring of external output release 0...1 USER
P065 Remote Start-Stop 0...3 USER
P066 Key switch 0...3 USER
P067 Function of input 42 0 = Pressure range, 1 = Monitoring USER
P070 Number of compressors during base load switching 1...4 USER
P071 Interval time until base load switching 0...250 h USER
P075 Base load switching: Max. pressure for pressure range 1 0 psi, 58 psi … max. pressure of compressor type USER
P076 Base load switching: Min. pressure for pressure range 1 44 psi … maximum P075 USER
P077 Base load switching: Max. pressure for pressure range 2 0 psi, 58 psi … max. pressure of compressor type USER
P078 Base load switching: Min. pressure for pressure range 2 44 psi … maximum P077 USER
No. Meaning Adjustment range Code
level