FOCUS 1.10 Parameter overview
Page 34 BOGE FOCUS compressor control for piston compressors
1.10 Parameter overview
84 Data reconciliation error in system pressure module
91
Mainboard input 42 signals fault –
see circuit diagram
X
Fault messages for special types
90 Lack of insulation X
92 Condensate drain of microfilter X
93 Condensate drain of dryer X
94 Dryer X
95 Microfilter X
96 Supply voltage X
Fault no. Meaning Compressor
switch-off
Note!
Parameters can be processed as described under Parameter Settings.
No. Meaning Adjustment range Code
level
P001 Language selection
DE = German; GB = English; IT = Italian;
RU = Russian; FI = Finnish; DK = Danish;
LT = Lithunian; SE = Swedish; PL = Polish;
ES = Spanish; PT = Portuguese; FR = French;
NL = Dutch; LV = Latvian; TR = Turkish;
CZ = Czech; HU = Hungarian
all
P012 Max. pressure for pressure range 1 0 psi, 58 psi...Max. pressure of compressor type USER
P013 Minimum pressure for pressure range 1 44 psi...maximum P012 less min. hysterisis USER
P014 Max. pressure for pressure range 2 0 psi, 58 psi...Max. pressure of compressor type USER
P015 Minimum pressure for pressure range 2 44 psi....maximum P014 less min. hysterisis USER
P020 Auto-Restart (automatic restart after power failure)
0 = Off,
1 = On
USER
P021 Auto-Restart time; time until restart after power failure 30 s...3600 s USER
P022 Suction pressure monitoring delay 0 s...3600 s USER