TECHNICIAN MENU
Keys
Sub-menu
Keys
Lines
Keys
Factory
settings
Field
1. ADVANCED CH
SETTINGS
C
1. CH power set
C
1. Maximum power 100%
C
100% 0 ÷ 100%
D B
D
2. Minimum power 0%
C
0% 0 ÷ 100%
D
2. CH temperatures
C
1. ABS max temperature
C
80°C 20 - 85°C
D
2. CH maximum setpoint
C
75°C 20 - 85°C
D
3. CH minimum setpoint
C
40°C 20 - 70°C
D
4. CH setpoint hysteresis
C
3°C 2 - 10°C
D
3. OTC parameters
C
1. Outside temp for max CH
C
-10°C -34 - 10°C
D
2. Outside temp for min CH
C
18°C 15 - 25°C
D
3. Outside temp for CH off
C
OFF
OFF/
7 - 30°C
D
4. OTC setpoint table
C
read only
D
5. OTC curve
C
read only
D
4. DHW pump settings
C
1. DHW post pump time
C
5’ 1’ ÷ 30’
D
5. CH anticycling timer
C
---> --->
2’ 0’ ÷ 15’
D
6. DHW request type
C
Outside sensor / room
therm. / 0-10V signal [%] /
0-10V signal [SP]
C
Room ther-
mostat
Outside sensor
/ room therm.
/ 0-10V signal
[%] / 0-10V
signal [SP]
2. ADVANCED DHW
SETTINGS
C
1. DHW power
C
1. Maximum power 100%
C
100% 0÷100%
D B
D
2. Minimum power 0%
C
0% 0÷100%
D
2. DHW temperature
C
1. Storage DHW setpoint
C
80°C 35÷85°C
D
2.
Instant DHW setpoint
C
60°C (*) 10÷65°C
D
3. DHW setpoint hysteresis
C
3°C 2÷10°C
D
3. DHW pump settings
C
1. DHW post pump time
C
30s Off/1÷180s
D
4. DHW priority
C
1. DHW status
C
Enabled
Enabled/
disabled
D
2. DHW priority timeout
C
Off Off/1÷60min.
D
5. DHW request type
C
---> --->
Switch
Contact/
Sensor
(*) In the event of a "sensor" type DHW request, the heating appliance heats the water to a temperature as set in point
“2.2.2“ of the technician menu + 20°C.
- 33 -