TECHNICIAN MENU
Keys
Sub-menu
Keys
Lines
Keys
Factory
settings
Field
3. SYSTEM SETTINGS
C
1.Boiler parameters
C
1.Ignition power
C
51% (*) 0÷100%
D B
D
2.Delay siphon check
C
10s 0÷60s
D
3.Number of boiler pump
C
Two pumps
Pump and
3-way valve/
Double pump
D
4.Pump speed max
C
100% 15÷100%
D
5.Pump speed min
C
30% 15÷100%
D
6.Anti-Legionella
C
Disabled
Enabled/dis-
abled
D
7. Heat exchanger protec-
tion
C
Enabled
Enabled/dis-
abled
D
8. Heat exchanger delta
C
10°C 5÷20°C
D
9.Modbus parameters
C
0 0÷255
D
10. 3-way valve travel time
C
10s 1÷255s
D
2. User interface settings
C
1.Language
C
Italiano
English/
Italiano
D
2. Select Units
C
Celsius
Fahrenheit/
Celsius
D
3. Set date
C
Enter the date
D
4.Set time
C
24 hours
24 hours/
12 hours
D
3.Maintenance settings
C
1.Service information
C
Enter tel. n°
D
2.Service due date
C
Enter date
4.DIAGNOSTICS
C
1.Boiler information
C
---> --->
--------
D B
D
2.Lockout history
C
---> --->
--------
D
3.Manual Test
C
---> --->
OFF OFF / 0-100%
(*) 51% for Multidea Evo 60.
25% for Multidea Evo 100.
30% for Multidea Evo 115.
- 34 -