Loading...
TECHNICIAN
MENU
Keys
Sub-menu
Keys
Sub-menu
Keys
Lines
Keys
Factory
settings
Field
5. USER
SETTINGS
C
1. Heating
C
1. CH setpoint
C
1. CH setpoint
C
75°C
20 - 85°C
D B
D
D
2.
Outside
temperature for
CH off
C
OFF
OFF /
7 - 25°C
2. ECO setpoint
reduction
C
---> --->
50°C 0 - 50°C
D
3. Scheduler set
C
1. Enable/disable on
board scheduler
C
Enabled
Enabled/
disabled
D
2. Scheduler set
C
Monday week days
D
2. DHW settings
C
1. DHW setpoint
C
---> --->
80°C 30 - 85°C
D
2. ECO setpoint
reduction
C
---> --->
20°C 0 - 50°C
D
3. Scheduler set
C
1. Enable/disable on
board scheduler
C
Enabled
Enabled/
disabled
D
2. Scheduler set
C
Monday week days
D
3. Holiday settings
C
1. CH holiday
setpoint
C
---> --->
20°C 20 - 85°C
D
2. DHW holiday
setpoint
C
---> --->
30°C 30 - 85°C
6.CASCADE
C
1. Cascade set
C
1. Cascade switch
delay
C
---> --->
60s 0÷255 s
D B
D
2. Cascade min
power
C
---> --->
14% 0÷100%
D
3. Single burner
power
C
---> --->
depending
on heating
appliance
0÷2550kW
D
4. Boiler for DHW
C
---> --->
0 0÷6
D
5. PI loop period
C
---> --->
4s 1÷15 s
D
6. Burner water
flow delay
C
---> --->
30s 0÷255 s
D
7. Different boiler
size
C
---> --->
Disabled
Enabled/
disabled
D
8. Cascade pump
speed max.
C
---> --->
100% 15÷100%
D
9. Cascade pump
speed min.
C
---> --->
30% 15÷100%
D
2. Cascade info
C
---> ---> ---> --->
Read only
D
3. Cascade
autodetect
C
---> ---> ---> --->
----- -----
- 35 -