Panel PCB: Quiescent current maximum 100mA
Battery: 12V/7 Ah, lead acid rechargeable
12V/17Ah, lead acid rechargeable
Low battery condition is below 11,0 VDC
Minimum battery condition is 10,8VDC
Certification: EN 50131-3 Grade-3 Environmental Class-II
Keypads:
IUI-AMAX4-TEXT (LCD Text Keypad)
Relative Humidity: 10%-95%
Operating Temperature: -10°C - +55°C
Input Voltage range: 10.8VDC - 13.8VDC
Current Consumption: standby 31mA
maximum 100mA
Cable requirements: four wire, AWG18 or AWG22
maximum length 200m (Panel to last KP)
maximum BUS 1 length 700m (max 14 devices, max 8
KPs)
maximum BUS 2 length 700m (max 14 devices, max 8
KPs)
EN type: EN = B, IK = 06, IP = 30
Certification: EN 50131-3 Grade-3 Environmental Class-II
IUI-AMAX3-LED16 (16 Zone LED Keypad)
Relative Humidity: 10%-95%
Operating Temperature: -10°C - +55°C
Input Voltage range: 10.8VDC - 13.8VDC
Current Consumption: standby 31mA
maximum 60mA
Cable requirements: four wire, AWG18 or AWG22
maximum length 200m (Panel to last KP)
maximum BUS 1 length 700m (max 14 devices, 8 KPs)
maximum BUS 2 length 700m (max 14 devices, 8 KPs)
EN type: EN = B, IK = 06, IP = 30
Certification: EN 50131-3 Grade-3 Environmental Class-II
IUI-AMAX3-LED8 (8 Zone LED Keypad)
Relative Humidity: 10%-95%
Operating Temperature: -10°C - +55°C
Input Voltage range: 12V normal