Invisible walk test
An invisible walk test allows you to test both controlled points and 24-hr points. Points
assigned to Point Indexes with the Invisible Point parameter set to Yes.
An invisible walk test includes points meeting the following criteria:
– Have a point source other than Unassigned
– Have a point index not set to Disabled (must be non-zero)
– Have a point index configured with the point type of 24-Hour, Part On, Interior, or Interior
Follower
– Are not service bypassed
Performing an invisible walk test:
1. Choose a keypad to conduct the test. Ensure that all areas are off (disarmed).
2. Enter your passcode and press [ENTER]. The keypad shows the number of points that
remain to be tested.
3. To view the list of points, press [ENTER] or [View untested points]. To scroll through the
list of points, use
/[PREV] or /[NEXT].
4. When your fault a point (open a door for example), the keypad emits a brief tone and
shows the name.