Figure 17.4: D125B to control panel wiring (B5512 shown)
Callout á…³ Description Callout á…³ Description
1 ᅳ Switched auxiliary power from the control panel’s
Output A (NC)
1
7 á…³ Supervised smoke detector to A LOOP negative
2 á…³Connection from an on-board point on the control
panel to Zone B
8 á…³ Supervised smoke detector to B LOOP positive
3 á…³ Connection from an on-board point on the control
panel to Zone A
9 á…³ Supervised smoke detector to A LOOP positive
4/5 ᅳ Connection to the control panel’s common (one
connection only)
10 á…³ Earth ground
6 á…³ Supervised smoke detector to B LOOP negative 11 á…³ Output A jumper (under cover) set to AUX PWR
1
You can also use Output B or C in conjunction with a D133 or D134 relay module.
Notification appliance circuit wiring
The control panel does not have an onboard NAC. Use a D192G Notification Appliance Circuit
Module for systems requiring a NAC.
Programming determines the output format and the conditions that activate the output. One
self-resetting circuit breaker protects against shorts. When using the output to activate
notification appliance circuits in UL Listed fire alarm applications, install a D192G Notification
Appliance Circuit module.
Refer to the D192G Notification Appliance Circuit Module Installation Guide (P/N: 4998122260)
for detailed wiring information and specifications.
17.4
17.5
Control Panel System wiring diagrams | en 83
Bosch Security Systems, Inc. Installation and System Reference Guide 2015.07 | 12 | F.01U.287.180