Installation, Operation, and Maintenance Manual
CA Series Heat Pumps - 8733851021 (2025/04) US
8 |
Operating Limits
Fluid Type Specication Cooling Heating
Air
Minimum ambient air temperature 50°F 40°F
Maximum ambient air temperature 100°F 85°F
Rated ambient air temperature 80°F 68°F
Minimum air coil entering air db/wb 65/57°F 45°F
Maximum air coil entering air db/wb 95/85°F 80°F
Rated air coil entering air db/wb 80/67°F 68/59°F
Liquid
Antifreeze Protection Required
— LWT <40°F
— EWT <50°F
Minimum water coil entering uid temperature 50°F
EXT 20°F
STD 50°F
Maximum water coil entering uid temperature 110°F 80°F
Rated water coil entering uid temperature
Water Loop 86°F 68°F
Ground Loop 77°F 32°F
Ground Water 59°F 50°F
Maximum operating water pressure Standard Unit 450psi/3,102kPA
Minimum operating water ow rate 1.5 GPM per ton
Note: Maximum and minimum operating limits may not be combined. Refer to Engineer Submittal Sheet on the product information page. (See the QR code in the
Troubleshooting section of the IOM).