Water-Quality Considerations
Table 8 Water Quality Table
Water Quality
Potential Problem Water Characteristic
Acceptable Value
Copper Cupro-Nickel
pH (Acidity/Alkalinity) 7–9 7–9
Scaling
Hardness (CaCO
3
, MgCO
3
)
< 350 ppm < 350 ppm
Ryznar Stability Index 6.0–7.5 6.0–7.5
Langelier Saturation Index -0.5 – +0.5 -0.5 – +0.5
Corrosion
Hydrogen Sulfide (H
2
S)
< 0.5 ppm* 10–50 ppm
Sulfates < 125 ppm < 125 ppm
Chlorine < 0.5 ppm < 0.5 ppm
Chlorides < 20 ppm < 150 ppm
Carbon Dioxide < 50 ppm < 50 ppm
Ammonia < 2 ppm < 2 ppm
Ammonia Chloride < 0.5 ppm < 0.5 ppm
Ammonia Nitrate < 0.5 ppm < 0.5 ppm
Ammonia Hydroxide < 0.5 ppm < 0.5 ppm
Ammonia Sulfate < 0.5 ppm < 0.5 ppm
Dissolved Solids < 1,000 ppm < 1,500 ppm
Iron Fouling
Iron (Fe
2
+ Iron Bacteria Potential)
< 0.2 ppm < 0.2 ppm
Iron Oxide < 1 ppm < 1 ppm
Erosion
Suspended Solids < 10 ppm, < 600 µm size** < 10 ppm, < 600 µm size**
Maximum Water Velocity 6 ft/sec 6 ft/sec
* No "rotten egg" smell present at < 0.5 ppm H
2
S.
** Equivalent to 30 mesh strainer
28 |
CL Series Heat Pumps — 8733838716 (2024/05)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch CL Series and is the answer not in the manual?

Bosch CL Series Specifications

General IconGeneral
BrandBosch
ModelCL Series
CategoryHeat Pump
LanguageEnglish

Related product manuals