EasyManua.ls Logo

Bosch CL Series - Water Quality Table and Recommendations

Bosch CL Series
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Water-Quality Considerations
Table 8 Water Quality Table
Water Quality
Potential Problem Water Characteristic
Acceptable Value
Copper Cupro-Nickel
pH (Acidity/Alkalinity) 7–9 7–9
Scaling
Hardness (CaCO
3
, MgCO
3
)
< 350 ppm < 350 ppm
Ryznar Stability Index 6.0–7.5 6.0–7.5
Langelier Saturation Index -0.5 – +0.5 -0.5 – +0.5
Corrosion
Hydrogen Sulfide (H
2
S)
< 0.5 ppm* 10–50 ppm
Sulfates < 125 ppm < 125 ppm
Chlorine < 0.5 ppm < 0.5 ppm
Chlorides < 20 ppm < 150 ppm
Carbon Dioxide < 50 ppm < 50 ppm
Ammonia < 2 ppm < 2 ppm
Ammonia Chloride < 0.5 ppm < 0.5 ppm
Ammonia Nitrate < 0.5 ppm < 0.5 ppm
Ammonia Hydroxide < 0.5 ppm < 0.5 ppm
Ammonia Sulfate < 0.5 ppm < 0.5 ppm
Dissolved Solids < 1,000 ppm < 1,500 ppm
Iron Fouling
Iron (Fe
2
+ Iron Bacteria Potential)
< 0.2 ppm < 0.2 ppm
Iron Oxide < 1 ppm < 1 ppm
Erosion
Suspended Solids < 10 ppm, < 600 µm size** < 10 ppm, < 600 µm size**
Maximum Water Velocity 6 ft/sec 6 ft/sec
* No "rotten egg" smell present at < 0.5 ppm H
2
S.
** Equivalent to 30 mesh strainer
28 |
CL Series Heat Pumps — 8733838716 (2024/05)

Table of Contents

Related product manuals