Troubleshooting
No compressor
operation but fan runs
(Continued)
X
Is the Fault LED
blinking two (2)
times?
Low pressure
fault—No or low air
flow
Check water valves and/or pumps for proper
operation. Check for water coil blockage.
Fouled or scaled
water-coil
Check for proper flow rate and water temperature,
but low-water-side temp rise in cooling.
Low pressure
fault—Low
refrigerant
Check refrigerant pressure with a gauge set.
X
Is the Fault LED
blinking three (3)
times?
Freeze fault, water
coil—No or low
water flow
Check water valves and/or pumps for proper
operation. Check for water coil blockage.
Freeze fault—Low
water temperature
Check water temperature—is it below 40° F
enterin
g? If heat pump is connected to a closed
loop with antifreeze check that the “FREEZE 1"
resistor on the UPM board has been cut to set the
unit to antifreeze mode (see UPM features on
page
#31).
Freeze fault - low
refrigerant
Check refrigerant pressure with a gauge set.
X
Is the Fault LED
blinking four (4)
times?
Condensate fault—
Poor drainage
Check condensate pan for high water level. Check
drain line for blockages, double trapping or
inadequate trapping.
Condensate fault—
Blocked return air
Check air filter and return air duct work for
blockage. Check that there is adequate space
between the return air opening and walls or other
obstructions on free return applications.
Unit Troubleshooting
Problem
Mode
Check Possible Cause Action
Cooling Heating
56 |
CL Series Heat Pumps — 8733838716 (2024/05)