Specification Tables
Operating Temperatures and Pressures
Cooling Heating
Model
Entering
Water Temp.
(°F)
Water
Flow (GPM)
Suction
Pressure (PSIG)
Discharge
Pressure (PSIG)
Water Temp.
Rise (°F)
Air Temp.
Drop (°F)
Suction
Pressure
(PSIG)
Discharge
Pressure (PSIG)
Water
Temp. Drop
(°F)
Air Temp.
Rise
(°F)
CL018
30°
3
— — — — 59–69 266–286 7–8 20–24
5
— — — — 64–74 272–292 4–5 21–25
40°
3
100–118 176–196 15–18 21–25 71–81 281–301 8–9 23–27
5
99–117 160–180 9–12 21–25 77–87 288–308 5–6 24–28
50°
3
102–120 203–223 14–17 20–24 85–95 297–317 9–10 26–30
5
101–119 187–207 8–11 20–24 93–103 306–326 6–7 26–32
60°
3
104–122 234–254 14–17 20–24 101–111 316–336 10–11 29–33
5
103–121 217–237 8–11 20–24 110–120 326–346 7–8 31–35
70°
3
106–124 267–287 14–17 19–23 118–128 335–355 12–13 33–37
5
105–123 251–271 8–11 20–24 129–139 349–369 7–8 35–39
80°
3
108–126 305–325 13–16 19–23 137–147 357–377 13–14 37–41
5
107–125 289–309 8–11 19–23 151–161 374–394 8–9 39–43
90°
3
110–128 346–366 13–16 19–23 158–168 382–402 15–16 41–45
5
109–127 332–352 7–10 19–23 — — — —
100°
3
112–130 391–411 12–15 18–22 — — — —
5
112–130 378–398 7–10 18–22 — — — —
CL024
30°
3
— — — — 55–65 256–276 8–9 18–22
6
— — — — 62–76 264–284 4–5 20–24
40°
3
105–122 213–231 20–23 21–25 66–76 269–289 10–11 21–25
6
102–119 178–196 10–13 21–25 76–86 279–299 5–6 23–27
50°
3
106–123 242–260 19–22 20–24 79–89 283–303 11–12 24–28
6
104–121 206–224 9–12 21–25 91–101 296–316 6–7 26–30
60°
3
108–125 274–292 19–22 20–24 93–103 298–318 13–24 27–31
6
106–123 238–256 9–12 20–24 108–118 314–334 7–8 30–34
70°
3
110–127 309–327 18–21 19–23 109–119 315–325 14–15 30–34
6
108–125 273–291 9–12 20–24 126–136 334–354 8–9 33–37
80°
3
112–129 347–365 18–21 19–23 126–136 334–354 16–17 33–37
6
110–127 312–330 9–12 19–23 147–157 357–377 9–10 37–41
90°
3
114–131 390–408 17–20 19–23 145–155 354–374 18–19 37–41
6
112–129 356–374 8–11 19–23 — — — —
100°
3
116–133 436–454 16–19 18–22 — — — —
6
114–131 404–422 8–11 18–22 — — — —
64 |
CL Series Heat Pumps — 8733838716 (2024/05)