3-6
Climate Class 6100i / 6000i / 8100i / 8000i
[4] 180deg. Energizing Control
This is the control system to moderate the speed by the current phase difference for higher efciency and lower noise of the compressor. The current
phase difference control is the control system paid attention to the interrelation between efciency and phase gap generated by the applied voltage
of motor and current in the coil of motor as shown in the gure below.
This control is the forced magnetization system independent of the location of rotor, detecting the phase difference between driving voltage phase
and line current phase owing in motor coil, and controls the modulation rate data to get the phase difference at the best efciency.