5-1
Climate Class 6100i / 6000i / 8100i / 8000i
CHAPTER 5. REFRIGERATION CYCLE
[1] SCHEMATIC DIAGRAM
s
1
4
C
2
Accumulator
3
Strainer
Expansion
valve
Heating Cooling
Outdoor unit
Condenser
Evaporator
Indoor unit
Reverse valve
Comp-
ressor
Flare coupling Flare coupling
3-way
valve
2-way
valve
Silencer
Coil
Antifreeze
pipe*
5
*
Only model CLC6101i-W 50 HE / CLC6101i 50 HE, CLC8101i-W 65 HE(T/S/R) have antifreeze pipe.
[2] STANDARD CONDITION
Indoor side Outdoor side
Dry-bulb Temp. (°C) Relative Humidity (%) Dry-bulb Temp. (°C) Relative Humidity (%)
Cooling 27 47 35 40
[3] TEMPERATURE AT EACH PART AND PRESSURE IN 3-WAY VALVE
Model CLC6101i-W 50 HE, CLC6101i 50 HE CLC6101i-W 65 HE, CLC6101i 65 HE
Cooling Heating Cooling Heating
Mode Max *1 Test Run *2 Max *1 Test Run *2 Max *1 Test Run *2 Max *1 Test Run *2
Ampere(A) 3.9 3.1 6.6 2.6 5.9 3.2 9.8 2.5
3-way valve pressure (MPaG) 1.0 1.1 3.1 2.1 0.9 1.1 3.4 2.1
Indoor Outlet Temperature (5) (°C) 14 15 43 32 12 16 50 31
Temperature(°C)
(1) 74 69 94 62 86 67 92 62
(2) 39 40 2 3 41 40 1 4
(3) 12 13 25 27 11 15 45 23
(4) 14 16 2 4 9 16 1 4