5-2
Climate Class 6100i / 6000i / 8100i / 8000i
Model CLC8101i-W 65 HE(T/S/R), CLC8101i 65 HE CLC6001i-W 25 E, CLC6001i 25 E
Cooling Heating Cooling Heating
Mode Max *1 Test Run *2 Max *1 Test Run *2 Max *1 Test Run *2 Max *1 Test Run *2
Ampere(A) 4.9 2.8 7.9 2.4 3.9 3.1 6.1 2.6
3-way valve pressure (MPaG) 0.9 1.1 3.1 2.0 1.0 1.1 3.0 2.2
Indoor Outlet Temperature (5) (°C) 13 16 46 30 14 15 42 31
Temperature(°C)
(1) 76 62 94 60 75 71 90 64
(2) 38 37 2 3 39 39 2 3
(3) 12 15 30 21 12 13 32 26
(4) 10 14 1 5 13 15 3 5
Model CLC6001i-W 35 E, CLC6001i 35 E CLC8001i-W 25 E(T/S/R), CLC8001i 25 E
Cooling Heating Cooling Heating
Mode Max *1 Test Run *2 Max *1 Test Run *2 Max *1 Test Run *2 Max *1 Test Run *2
Ampere(A) 6.1 3.2 7.8 2.6 3.1 3.8 5.7 2.5
3-way valve pressure (MPaG) 0.9 1.1 3.3 2.2 1.1 1.1 2.8 2.0
Indoor Outlet Temperature (5) (°C) 13 16 45 31 15 16 40 30
Temperature(°C)
(1) 85 70 94 64 66 64 89 61
(2) 40 39 2 3 37 37 2 3
(3) 10 14 34 26 14 15 23 21
(4) 7 16 2 5 14 15 4 5
Model CLC8001i-W 35 E(T/S/R), CLC8001i 35 E
Cooling Heating
Mode Max *1 Test Run *2 Max *1 Test Run *2
Ampere(A) 4.9 2.8 7.9 2.5
3-way valve pressure (MPaG) 0.9 1.1 3.1 2.0
Indoor Outlet Temperature (5) (°C) 14 16 44 30
Temperature(°C)
(1) 77 63 98 61
(2) 38 37 2 2
(3) 12 15 25 20
(4) 12 15 1 5
*1 To enter cooling max, start the unit with remote control setting 16°C and high fan speed.
Check the data within 30min after start cooling.
*2 Refer to installation manual for how to enter test run.