EasyManua.ls Logo

Bosch Compress 3000 DW FI Series - Connecting the Ducts; Connecting the Water Pipes

Bosch Compress 3000 DW FI Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 720 809 134 (2013/09) Compress 3000 DW FII
12 | Installation
5.3 Connecting the ducts
The air inlet can be located in the installation room, in a
different room or outside. In the latter two cases, air inlet ducts
must be installed.
When choosing a room for the air inlet, observe the average air
temperature and required air flow rate ( Tab. 3). In order to
minimise air resistance, lay the air inlet and outlet ducts
160 mm) as straight as possible.
The length (L
eq
) of the air inlet and outlet ducts must not
exceed the following values:
30 m at fan speed SP1
To ensure that condensate forming in the air inlet and air outlet
ducts drains from the appliance:
Install air ducts horizontally or at a slight angle to the air inlet
and air outlet apertures on the top side of the appliance.
Installation with ducts
▶ActivateDuct function ( page 24, chapter 8.6.4).
5.3.1 Open flue operation
If the heat pump is operated with air from the installation
location, the volume of the room must be at least 20 m
3
.
5.3.2 Outdoor air operation
If the pump is operated with outdoor air, the ducts must be
protected against the weather using the correct end pieces.
Fig. 9 Equivalent duct length (L)
[1] Air inlet
[2] Air outlet
5.4 Connecting the water pipes
NOTICE: Possible damage to external
casing!
Do not tilt the appliance on his feet more
than 20°.
To ensure maximum appliance performance
and to prevent condensation forming on the
external duct walls, use thermally and
acoustically insulated ducts.
Air inlet
(IN)
Air outlet
(OUT)
L
eq
0.5 m duct 0.5 m
1m duct 1.0m
2 m duct 2.0 m
10 m hose 19.0 m
45° elbow 0.9 m
90° elbow 2.0 m
90° flexible curve 2.3 m
Weather grille 8 m 4m
Roof output 7 m 4m
Table 4
L Fan speed
1)
1) chapter 8.6.4
Up to 30 m SP1
Table 5
Never close the water shut-off valve during
operation (Fig. 6, [4]).
L
2T
L
T1
L1
C1 C2
L2
L4
L3
L = L1+C1+L2
T1
L = L3+C2+L4
L=L +L
SP1: L 30m
T2
T1 T2
2
1

Table of Contents

Related product manuals