6 720 809 134 (2013/09) Compress 3000 DW FII
24 | Operation
Set the time for disinfection.
Select the time using the "+" and "-" buttons.
▶Press "OK".
As soon as the temperature reaches 70 °C, the appliance
switches back to the previously set operating mode.
Activating the manual "Leg" function
Call up the "Leg" function and press "OK".
" " flashes on the display.
▶Press "OK".
The "Leg" function is active.
As soon as the temperature reaches 70 °C, the appliance
switches back to the previously set operating mode.
Cancelling the "Leg" function.
Call up the "Leg" function and press "OK".
" " flashes on the display.
Press "+" until the display shows "LstP".
▶Press "OK".
The current Legionella program is cancelled.
8.6.4 « Duct » - use of ducts
Fig. 36 « Duct » function
Switching on the « Duct » function
Select « Duct » function and press « OK ».
The display shows “dOFF”.
Press « + » or « - » to define the use of ducts:
« dOFF » : installation without ducts
« dON » : installation with ducts
▶Press «OK».
8.6.5 "Purg" - Drain
The "Purg" function can be used to drain water from the system.
Fig. 37 "Purg" function
Switching on the "Purg" function.
Call up the "Purg" function and press "OK".
The pump is switched on.
The display indicates the time remaining until the draining
procedure is complete (in minutes).
After 5 minutes, the appliance reverts to the previously
selected operating mode.
8.6.6 "Fset" - Default settings
The "Fset" function can be used to restore the default settings.
Fig. 38 "Fset" function
Switching on the "Fset" function
Call up the "Fset" function and press "OK".
The display shows "Fset".
▶Press "OK".
After 10 seconds, the default settings are restored
( chapter 8.9).
8.7 "Info" submenu - Information
With the "Info" function, it is possible to display the total
consumption for the last 30 days.
The DHW temperature is automatically set to
70 °C.
To repeat the disinfection process, you must
reactivate it.
This only ends the current program; the
weekly repetition is still active.
6720807839-01.1V
6720801967-02.1V
6720804054-10.1V