Settings in the service menu
Condens 8300i W – 6721841531 (2022/10)
32
Menu 3: Basic settings
Press the ( key and * key simultaneously until the display shows
L.1.
Press the key repeatedly until L.3 appears.
To confirm the selection: press OK key.
Selecting and setting the service function.
The factory settings are depicted as highlighted in the following table.
Table 17 Menu 3: Basic settings
Service function Settings/adjustment range Remark/restriction
3-b1 Maximum approved heating capacity 50 … 100 % (depending on the appliance output) Set the heating capacity in percent.
Measure the gas rate.
Compare the measurement with the setting
tables ( page 59). Correct the setting in
the case of any deviation.
3-b2 Time interval between stopping and
starting the burner in heating mode
•3 10 … 60 minutes The time interval determines the minimum
waiting time between switching off the burner
and switching it back on (standby period).
3-b3 Temperature differential for restarting
the burner
•-15 -6 … -2 K ( °C) The difference between the current flow
temperature and the set flow temperature until
the burner is switched on.
3-C4 Turbine signal delay 2 … 16 × 0.25 seconds The delay prevents sudden changes in the water
supply pressure from causing the burner to
briefly operate although no water is drawn off.
3-C5 Delay of DHW mode (solar mode) 0 (not active) ... 50 seconds DHW mode will be suppressed until the DHW
temperature sensor detects if the water
preheated by solar energy has reached the
desired DHW temperature.
Set the DHW mode delay according to the
system conditions.
3-C6 Time between DHW mode and change
to heating mode
•0 1 ... 30 minutes After hot water has been drawn, the device
remains in DHW mode for the set time.
3-C8 Thermal desinfection OFF
•ON
With thermal disinfection activated, when
drawing hot water the water is heated 70 °C for
a duration of 10 minutes.
After 10 minutes or after drawing hot water 3
minutes long, the thermal disinfection ends
automatically.
3-CA DHW Mode 0: comfort mode, the device is continually kept at
the set temperature.
1: ECO mode, only heat-up to the selected
temperature when hot water is being drawn.
3: intelligent
Short waiting time in comfort mode, when
domestic hot water is extracted. The device
therefore switches on, even if no domestic hot
water is extracted.
3-d1 Pump characteristic 0: Pump output proportional to the heat output
1: constant pressure 150 mbar
2: constant pressure 200 mbar
3: constant pressure 250 mbar
4: constant pressure 300 mbar
5: constant pressure 350 mbar
6: constant pressure 400 mbar
In order to save energy and reduce any flow
noise, set a low pump curve ( sec 13.5,
page 59).
3-d2 Pump control mode OFF
•ON
ON: Save energy: intelligent shutdown of
heating pump for heating systems with
weather-compensated controller. The
heating pump is only switched on if required.
3-d3 Min. output of the heating pump 10 ... 100 % Pump output at minimum heat output. Only
available with pump characteristic 0.
3-d4 Max. output of the heating pump 10 ... 100 % Pump output at maximum heat output. Only
available with pump characteristic 0.
3-d6 Overrun time of the heating pump in
heating mode
•1 2 … 60 minutes
24 hours
The pump overrun begins at the end of the heat
demand by the heating controller.