D6412/D4412 Operation and Installation Guide
Page 22 © 2003 Bosch Security Systems45349E
D6412/D4412
Power Outputs
5.5 Output Programming
Programmable Output 2 (PO2) can be configured as a supervised siren driver. See Global Output Configuration in the D6412/
D4412 Program Entry Guide (P/N: 45351) for programming instructions. When programmed as a siren driver, PO2 draws
power from the Alrm + terminal. When connected to a 4 horn/speaker, PO2 draws 380 mA of power. When connected to
an 8 horn/speaker, it draws 330 mA of power. Use the appropriate current draw in your total alarm power calculation.
Programmable Output 1 (PO1): PO1 terminals can be configured as an alarm power output. JP2-PO1 Jumper
must be closed. The default configuration for Programmable Output 1 makes it a dry contact, normally open
relay. The PO1 Jumper is open. See Figure 5 for jumper location.
Programmable Output 2 (PO2): Output PO2 can be used with Alarm+ as a supervised siren driver. Connect an
approved 4 or 8 siren. Alternatively, PO2 can sink up to 500 mA 12 VDC. For larger loads, use a Bosch Security
Systems D133 Relay Module or Bosch Security Systems D134 Dual Relay Module.
Programmable Outputs 3 and 4 (PO3 and PO4): Outputs PO3 and PO4 can be configured for Alarm Output.
These outputs can sink up to 500 mA 12 VDC each. For larger loads, use a Bosch Security Systems D133 Relay
Module or Bosch Security Systems D134 Dual Relay Module.
Power restricted for fire and combined fire/burglary systems: Use the Fire System Power Formula in Section 5.4.1 Available
Power to calculate the current available for fire and combined fire/burglary systems.
Unexpected Output at PO1 to PO4: If these outputs do not provide the alarm output you expect:
Check the programming for Programmable Outputs in the Outputs section of the D6412/D4412 Program Entry
Guide (P/N: 45351).
Check the Point Index Configuration section of the D6412/D4412 Program Entry Guide to verify the points you
are activating are programmed for alarm output.
I
MPORTAN
T
If Programmable Output 2 is configured as a supervised siren driver (in combination with the Alrm + terminal),
you must connect a 4
or 8
siren/speaker to PO2 to clear the siren/speaker supervision trouble.
PO 1 Jumper
R
Y
G
B
Alrm
+
PO1
AB
L-1
+
-
JP2-PO1
Select
Programmable Outputs 1-4
Figure 5: On-Board Outputs