D6412/D4412 Operation and Installation Guide
Page 10 © 2003 Bosch Security Systems45349E
D6412/D4412
Overview
2.0 Overview
Figure 1: System Configuration
2.1 Specifications
Voltage Input
Primary:
18 VAC 22 VA class 2 plug-in transformer CX4010 (D1825)
Secondary:
12 VDC, 7 Ah sealed lead acid rechargeable battery or 12 VDC, 18 Ah sealed lead acid
rechargeable battery.
Current Requirements
Panel:
100 mA
See Appendix : Approved Applications Compliance Guide for the current requirements of other
system components.
Power Outputs
Continuous:
Up to 600 mA maximum at 11.5 VDC to 12.4 VDC (continuous supply) total for all devices
and outputs for non UL applications.
Note: Up to 400 mA at 11.5 VDC to 12.4 VDC for UL Listed burglary applications, 120 mA for Fire and
Combined Burglary/Fire (continuous supply) total for all devices and outputs.
Alarm
Power:
400 mA for Fire and combined Fire/Burglary; 1500 mA for UL Burglary; 1850 mA for other
(not investigated by UL). Applies to all four outputs combined. See the Outputs section of the
D6412/D4412 Program Entry Guide (P/N: 45351).
Battery Discharge/Recharge Schedule
Discharge
Cycle:
AC Off: Command centers indicate trouble. AC Fail Report sent as programmed.
13.8 VDC:
Charging Float Level.
12.1 VDC: Low Battery trouble at command centers.Low Battery Report as programmed.
10.2 VDC: Panel shuts down as voltage falls below 10.2 VDC.
Recharge
Cycle:
AC On: Panel restarts, battery charging begins, AC Restoral Report sent as programmed, AC
trouble clears from command centers.
13.0 VDC: Battery Restoral Reports sent, battery trouble clears from command centers.
3.8 VDC: Battery float charged.
DX2010
Point Expansion Module
DX3010
Octo-Output Module
Use command centers and/or keyswitches to
arm the panel by area. Each area can have its
own account number or areas can be grouped
together with a common account number.
Points of protection are assigned to areas.
Control Panel
8 On-Board
Sensor Loops
4 On-Board
Outputs
D8132 Modules provide
additional power for command
centers and other powered
devices.
DX4010
Serial Interface Module
(for connection of serial printer
or other RS-232 device).
RF3224 Premises
RF Receiver
(up to 4 RF keypads
and 32 keyfobs)
DX3020 Module
Provides control for
X-10 modules.