D6412/D4412 Operation and Installation Guide
Page 54 © 2003 Bosch Security Systems45349E
D6412/D4412
13.2.2 Service Start/Service End Reports
After you enter your installer passcode and press [Cmd 41] to enter the Installer’s Mode, the panel sends a Service Start
Report. When you exit the Installer’s Mode, it sends a Service End Report.
AUXILIARY
JP1
Installer
INSTALLER SWITCH
NORMAL (OPEN)
INSTALLER SWITCH
LOCKED (CLOSED)
Figure 44: Installer Switch
13.3 Installer’s Menu
13.3.1 Press [1] for Bell Test
The panel activates the Bell Time (1-5) and Alarm Output (1-8, 1-9, 1-10, 1-11, and 1-12.) functions for 3 seconds. See
Outputs in the D6412/D4412 Program Entry Guide (P/N: 45351) for a complete description of output functions.
13.3.2 Press [2] for Strobe Test
The panel activates the Strobe Output function (1 to 9) and waits for the installer to press the [Cmd] key to end the test. If
the installer fails to press the [Cmd] key within 20 min., the panel automatically terminates the strobe test.
13.3.3 Press [3] for Battery Test
The battery test causes the system to run on battery only for four min. If the battery voltage falls below 12.1 V during the
four min. test or if the battery is missing, the system restores AC power and displays a system trouble at all keypads.
13.3.4 Press [4] for Test Report
When you press the [4] key, the panel tries to send a Test Report. If there is a system trouble present at the time of the test,
the panel sends a Test, Off Normal Report.
The Test Report follows the routing for the Automatic Test Report.
If the test communication is unsuccessful, the panel creates a system trouble and a communication failure.
MPORTAN
This Test Report is the only report sent when the Installer Switch is closed. No other reports are sent when the
Installer Switch is closed.
13.3.5 Press [5] for Point Status
Pressing [5] displays the sensor loop status for the first location in the system. The location, area, point number, and
electrical status (open, short, or normal) are shown. See Locations in the D6412/D4412 Program Entry Guide (P/N: 45351)
for a complete description of the relationship between locations, areas, and points.
Pressing the [*] key advances the display to the status for the next point.
Pressing the [Cmd] key exits the Point Status Mode.
Installer’s Keypad and Installer Mode