D6412/D4412 Operation and Installation Guide
Page 66 © 2003 Bosch Security Systems45349E
D6412/D4412
Appendix A: Approved Applications Compliance Guide
Household Burglary
(Grade A)
Household Fire
Household Fire/Burglary
Combined
Central Station Burglary
(Grade C)
Police Connected
Burglary
Local Burglary
Mercantile (4 hrs.)
Commercial
Mercantile (72 hrs.) Bank
Safe/Vault Alarm
Proprietary Burglary
NFP Standard
72 72
Min.Hrs. of
Standby Battery
4 24 hrs. +
4 min.
24 hrs. +
4 min.
4444724
Entry/Exit
Time (sec.)
45/60 45/60 45/60
Bell Time (min.)
4 4 4 15 1515151515
D2203 Enclosure
Included w/panel No NoNoNoNoNo
D8103 Enclosure*
Optional Choose
One
No No No No No
D8108A Enclosure
Optional Req Req Req Req Req
D8109 Enclosure
Optional No No No No No
D126 Battery (7 Ah)
Req Req Req Req Req Req Req No Req
D1218 Battery (18 Ah)
Opt Opt Opt Opt Opt Opt Opt Req Opt
D127 Reversing Relay
Opt Opt Opt Opt Opt Opt Opt Opt Opt
D132A Smoke
Detector Reversing
Relay Module
Required if D192C is not used. Use D132A with compatible smoke detectors only.
D164 Telephone Card
Required to connect panel to RJ131X Telco Block
D192C NAC
Supervision Module
Required if D132A and compatible smoke
detectors are not used.
D621, D623, D625
Command Center
1+ 1+ 1+ 1+ 1+ 1+ 1+ 1+ 1+
D262 Smoke Detector
Head/D621 Base
1
•
1
•
D282THS Smoke
Detector w/ Sounder
Use with D132A.
D431, D435, D438,
D440, D442, D448
Indicating Device
1+ 1+ 1+ Opt
♦♦♦♦♦
CX4010 Transformer
Required for all applications.
D8004 Transformer
Enclosure
Opt Opt Opt Opt Opt Opt
D8122 Derived
Channel STU
Optional. Contact Telco for the availability of derived
channel service.
D8130 Release Module
Optional
Key
No Not acceptable for
this application.
Req Required for this
application.
Opt Optional for this
application.
1+ 1 or more
required for this
application.
Consult the
appropriate
standard.
1
•
At least one
detector required.
You can substitute
other 2-wire
detectors listed for
use with the
D6412/D4412.
You can use D262
with D270
4-wire detectors.
You must use a
listed power
supervision relay
with 4-wire
detectors.
♦
UL Listed bell
(siren) housing
required for
burglary alarm
bell or siren
(Rothenbuhler
5110 Bell).
Empty
Cell
Not used for this
application.
∗
Not to exceed
these Entry/Exit
Delay limits for
UL installations.
∗∗
D101 for this
application.
Enclosures
Bosch Security Systems offers three optional enclosures for the control panel.
1. The D8103 enclosure is suitable for residential fire and/or burglary installations and commercial burglary
applications that do not require attack resistance or approval by Factory Mutual or NYC-MEA. (See
Appendix B: System Chart for acceptable applications.)
2. The D8108A is attack resistant. It is intended primarily for UL commercial burglar alarm and mercantile
safe and vault applications requiring a local bell. You can use the D8108A in any burglar or fire alarm
application where the 5591 or D8109 enclosure is suitable. UL lists the D8108A for all commercial fire
alarm applications. The D8108A is approved by Factory Mutual, California State Fire Marshal, and the
New York City Materials and Equipment Acceptance System.
3. The D8109 is normally used for commercial fire alarm applications. UL lists the D8109 for all commercial
fire alarm applications. The D8109 is approved by the California State Fire Marshal, NYC-MEA and FM.
MPORTAN
All references to NFPA and related requirements are based upon compliance with the 1993 edition of NFPA 72,
National Fire Alarm Code. Since installation specifications are nearly always based on a specific edition of a
standard that has been legally adopted by the Authority Having Jurisdiction (AHJ), earlier editions of NFPA
standards generally apply. Consult the appropriate AHJ for confirmation.
A-2 System Chart