D6412/D4412 Operation and Installation Guide
D6412/D4412
Page 67© 2003 Bosch Security Systems 45349E
Appendix A: Approved Applications Compliance Guide
The D6412/D4412 control panel is suitable for Police Station connect applications, including Grade A Mercantile Premises
and Grade A Mercantile Safe and Vault alarm systems. Suitable for Grade AA Mercantile Premises and Grade AA Mercantile
Safe and Vault alarm systems when the Model D6412/D4412 DACT unit is installed in conjunction with the Model D8122
derived channel subscriber terminal unit. For all Police Station applications and grades, the Model D8108A Attack Resistant
Enclosure with a UL Listed local sounding device is required. Per UL 365, keyswitches mounted outside the protected area
must employ high security locking cylinders complying with the requirements for key locks, UL 437. Tamper protection must
also be provided.
The D6412/D4412 control panel is suitable for Local, Grade A Mercantile Premises and Local, Grade A Mercantile Safe and
Vault alarm systems. For all local applications and grades, the D8108A Attack Resistant Enclosure and a UL Listed local
sounding device are required. Per UL 609, when keyswitches are mounted outside the protected area, tamper protection must
be provided.
The D6412/D4412 control panel is suitable for Central Station, Grade C applications. It is suitable for Central Station, Grade
B applications when the Model D6412/D4412 DACT unit is installed with a UL Listed local sounding device. Also suitable for
Central Station Mercantile, Grade AA applications when installed with the Model D8122 derived channel subscriber terminal
unit.
A-3 System Wiring Diagrams, Issue A
Aux
Pwr
+
Aux Pwr -
400 mA for Fire and
Combined Fire/
Burglary;
1500 mA for UL
Burglary;
1850 mA for other*
Applies to all four outputs combined.
Use compatible
NAC such as
Bosch Security
Systems D440
Powered Sensor Loop
suitable for Two-Wire
Smoke Detectors 2.2 k
Resistor required at End of
Line. For compatible smoke
detectors, see D6412/D4412
Technogram (P/N:46928).
The UL Panel
Compatibility Identifier = B.
Also available for Four-
Wire Smoke Detectors such as Bosch Security Systems
D273TH.
Note 1
: A supervisory alarm output module must be used
on these terminals for household fire applications
Note 2
: Jumper J2-PO1 must be in place for connection
to NAC or other powered alarm device.
Installer Switch
Disables Arming,
Reports, and Relays.
Lock for local
programming.
All external connections are inherently Class 2 power limited.
256
3
4
L-3 Com L-4 L-5 Com L-6 L-7 Com L-8PO3 PO2
Alrm
+
AB
+-
Com L-2PO4
PO1
L-1
Installer
Keypad
Connect
Lock
Installer
Switch to
program.
Earth Ground
Do not connect to a receptacle
controlled by a switch. Do not
share with
other
equipment.
D4412 uses a
CX4010 UL Listed
Class 2 Transformer
18 VAC 22 VA 60 HZ
Green
Yellow
Red
Black
ABCD
P
S
Keypads, Expanders
Printer modules &
Communication modules
(up to 19 total devices)
P
S
P
S
P
S
Data
Data
(a) The delay (power-up) (start-up) time marked on the
installation wiring diagram of the smoke detector or
on the installed smoke detector(s) is to be used.
System Delay Chart
Circuit
(Loop)
Control Unit
Delay - Sec
Smoke Detector
Model Delay - Sec
116 sec
(a)
R1
T1
R
T
Red
Brown
Green
Gray
R1
T1
R
T
Incoming
Phone
Line
Use Bosch
Security Systems
D164
Phone Cord
or equivalent.
Ground Start
requires
D133/D134.
78
Supervised Loops
Open 7.7 to 14.0 VDC
Normal 6.3 to 7.3 VDC
Short 0.0 to 6.0 VDC
2.2 k
Resistor
(P/N:47819)
Required at End of Line
1
+
-
see
Note 1
Auxilliary Powered Devices 11.5 to 12.4 VDC. Below 10.2 VDC, the D4412 stops processing Loop inputs.
With 7.0 Ah battery,
120 mA for 24 hrs for Fire and Combined Fire/Burglary,
400 mA for 4 hrs for UL Burglary.
600 mA for other*
Include keypads in calculations.
POWER SUPPLY REQUIREMENTS
The Power Supply provides a maximum of 600 mA for the Control Panel
and All Accessory Devices. For System loading, See D6412/D4412 Installation Instructions
(P/N:45349). Requirements for battery standby time may reduce
allowable output.
CAUTION
: See D6412/D4412 Installation Instructions (P/N:45349) for power requirements relating
to terminals [Alrm+] and [+Aux].
PO1 Terminals can be configured
as an alarm power output. JP2-
PO1 Jumper must be closed.
Maximum charging
current is 1.1 A.
BATTERY
: Replace
every 3 to 5 years.
Use Bosch Security
Systems Model
D126, 12 V 7 Amp HR
Sealed Lead Acid
Battery for Burglary or
Combination Fire and
Burglary Systems. For
additional load or
standby power, refer
to battery calculation
sheet in D6412/D4412
Installation Instructions
(P/N:45349).
Outputs PO3 &
PO4 can sink up
to 500 mA 12
VDC. Use D133/
D134 for larger
loads.
See D6412/D4412 Installation Instructions
(P/N:45349) for System Wiring Diagram
Premises
Phone
JP2
Output PO2 can be used
with Alarm+ as a
supervised siren driver.
Connect an approved
4 or 8
siren.
Alternatively, PO2 can
sink up to 500 mA 12
VDC. Use D133/D134
for larger loads.
P/N
25899
* Not investigated by UL.
Supervised with 2.2 k
EOL Resistor
(P/N: 47819).
Typical Initiating Devices
are Door Contacts NO/NC,
Floor Mats, Motion
Sensors, Glass Break
Detectors, etc.