Legionela disinfection:
From both manual (instantaneous) and automatic (weekly operation) selection, the legionela function will assure
the COMBI mode operation during the 1
st
24 hours (compressor until T
top
> 60ºC and only E-Heater until T
top
>
70ºC), nevertheless and if this was not enough to complete LEG function, the HP switch to FULL mode.
Stop condition:
T
top
> 70ºC or T
bottom
> 60ºC or Leg function time > 48h (24 hours in combi and 24 hours in FULL)
Stop condition (only for HP270-3):
T
discharge
> 60ºC during 10 min or Leg function time > 48h (24 hours in combi and 24 hours in BOOST)
Conditions for air-defrost sequence:
Air defrost sequence is activated in both +5ºC / +35ºC and -10ºC / +35ºC models when 5ºC < T
air
< 10ºC for more
than 60 min and compressor is ON for more than 60 min as well with recurrence determined by the temperature
measured by T
bottom
sensor.
Pict.7 – Status diagram for air defrost