Operation Modes (HP 270-2)
Combi Mode
(default selection from factory)
T
set
= 50ºC / 54ºC (default value depends
software version)
Temperature adjustment: 30ºC to 70ºC
Temperature adjustment: 30ºC to 60ºC
Temperature adjustment: 30ºC to 70ºC
New Platform (HP270-3 and HP200/250-1)
Combi Mode
(default selection from factory)
T
set
= 53ºC
Temperature adjustment: 30ºC to 70ºC
Temperature adjustment: 30ºC to 60ºC
Temperature adjustment: 30ºC to 70ºC
Table 1 – Operation Modes
Conditions for operation:
The heat pump compressor is activated according to the following conditions and control unit settings,
nevertheless, following sequence is always verified when connecting to the main power, when an error code is
reseated or the appliance stops due to reaching the selected temperature.
In the current service manual version, the software specific functions are indicated according Software Version at
control unit identification sticker.
1 – 3 min: Standby (Duct off)
or
1 – 2 min: Standby (Duct on)
3 – 4 min: Fan activation when
Duct OFF
or
2 – 4 min: Fan activation when
Duct ON
> 4 min: Compressor and water
pump activation