Page 15 from 56 6-720-821-364 SM HP270 – 250 - 200 2016/12 en
Pict.13 – Compressor Connection Detail
Compressor
- After turn ON the appliance, the compressor should operate for more than 5 minutes.
- The compressor should be operated for more than 20 seconds within 15 minutes after charging refrigerant
into the system to ensure proper lubrication
- The compressor should never be operated while under vacuum, otherwise, internal arcing can damage
some parts.
- The compressor should not be left opened in the atmosphere for more than 5 minutes.
Highly
(model WHP01900BSV)
Specification from supplier:
- Standard condition: 1.9 kW of heating
capacity / 475 W input
- Thermal protection included
(temperature limiter: opens at 160ºC,
closes at 70ºC)
- 270 ml of oil capacity
In case of check capacitor, discharge
electric charge with a resistance of
20kΩ
OK – scale decrease to 0 and pass to ∞
Not OK – 0Ω