118 en | Plena Voice Alarm System
9922 141 1037x (V2.16) | V0.6 | 2011.09 Installation and Operation manual Bosch Security Systems B.V.
4 General Requirements
Clause / Requirement Compliance Signature
4.1 General
Praesideo is compliant.
4.1.1 If an optional function with requirements
is included in the VACIE, then all the
corresponding requirements shall be met (see
Annex B).
The following optional functions, with
requirements, are included in Plena Voice
Alarm System:
Audible warning (7.3)
Manual silencing of the voice alarm
condition (7.6.2)
Manual reset of the voice alarm
condition (7.7.2)
Voice alarm condition output (7.9)
Indication of faults related to the
transmission path to the CIE (8.2.6)
Indication of fault related to voice
alarm zones (8.2.7)
Voice alarm manual control (10)
Emergency microphone(s) (12)
Microphone priority (12.2)
Redundant power amplifiers (13.14)
The following optional functions with
requirements are not included in Plena
Voice Alarm System:
Delay(s) to entering the voice alarm
condition (7.4)
Phased evacuation (7.5)
Output to fire alarm devices (7.8)
Disabled condition (9)
Interface to external control device(s)
(11)
4.1.2 If functions other than those specified in
this European Standard are provided, they
shall not jeopardize compliance with any
requirements of this European Standard
4.2 Combined VACIE and CIE
When the VACIE and CIE are combined they
may share common indications, manual
controls and outputs (see Annex F). In this
case, the following shall apply:
This requirement is not applicable. In Plena
Voice Alarm System, the Voice Alarm
Control and Indicating Equipment (VACIE)
is not combined with a fire alarm Control
and Indicating Equipment (CIE).
a single fault in the CIE shall not adversely
affect the mandatory functions of the
VACIE;
b indication(s) and manual control(s) of the
voice alarm condition shall be clearly
identifiable, with the exception of the
optional audible warning.
4.3 Power supply Plena Voice Alarm System is compliant.