Plena Voice Alarm System Technical data | en 95
Bosch Security Systems B.V. Installation and Operation manual 9922 141 1037x (V2.16) | V0.6 | 2011.09
Mic/line input with VOX functionality
BGM
Line out
External power amplifier
10.1.2 Voice Alarm Router
Electrical
Interconnection
Type: 3-pin XLR, 6.3 mm jack socket, balanced
Sensitivity: 1 mV +1/-3 dB (mic), 1 V +1/-3 dB (line)
Impedance: > 10 kΩ
VOX threshold: 500 µV (mic), 500 mV (line)
Type: Cinch, stereo converted to mono
Nominal input level: 500 mV
Type: 3-pin XLR, 6.3 mm jack socket, balanced
Nominal output level: 1 V
Maximum output level: 1 V
Type: 3-pin XLR and screw terminals
Controller output/Amplifier input: 1 V
Controller input/Amplifier output: 100 V
Mains voltage: 230/115 V(AC), ± 10%, 50/60 Hz
Mains current: 0.2 A (system idle)
0.3 A (maximum load)
Max. mains inrush current: 1.5 A (for mains voltage of 220 - 240 V)
3 A (for mains voltage of 100 - 120 V)
Battery voltage: 20.0 to 26.5 V(DC)
Battery current: 0.5 A (system idle)
1.5 A (maximum load)
NOTICE!
Maximum load means maximum power out, maximum load 24 V(DC) out and maximum
number of call stations.
Voice Alarm Router : RJ45 socket, CAN bus; max. 2 routers
External power amplifiers: 3-pin XLR and screw terminals, max. 5 A;
max. rated output 1000 W