120 en | Plena Voice Alarm System
9922 141 1037x (V2.16) | V0.6 | 2011.09 Installation and Operation manual Bosch Security Systems B.V.
5 General requirements for indications
Clause / Requirement Compliance Signature
5.1 Display and functional conditions
Plena Voice Alarm System is compliant.
5.1.1 The VACIE shall be capable of
unambiguously indicating the following
functional conditions, as described in Clauses
6 to 9:
– quiescent condition;
– voice alarm condition;
– fault warning condition;
– disablement condition (option with
requirements)
See Clauses 6 to 9.
Plena Voice Alarm System does not have a
disablement function.
5.1.2 The VACIE shall be capable of being
simultaneously in any combination of the
following functional conditions on different
voice alarm zones:
The Plena Voice Alarm System system is
capable of being simultaneously in the
voice alarm condition and in the fault
warning condition.
– voice alarm condition; The voice alarm condition is indicated on
each call station (system status LED),
remote control or fireman’s panel and on
the display of the controller This system
wide indication can be combined with the
indication of the fault warning condition:
the controller gives an audible warning on
EMG condition that has priority over the
audible fault signal. EMG condition is
indicated by a red LED, faults by
corresponding yellow LEDs, therefore both
conditions can be indicated
simultaneously.
– fault warning condition; The fault warning condition is indicated on
each call station (system status LED),
remote control or fireman’s panel and on
the display of the controller (faults menu).
This system wide indication can be
combined with the indication of the voice
alarm condition The display of the
controller can indicate both the voice alarm
condition and the fault warning.
– disablement condition (option with
requirements).
The optional disablement condition is not
implemented in Plena Voice Alarm System.
5.2 Indication display Plena Voice Alarm System is compliant.
All mandatory indications shall be clearly
identifiable, except where otherwise specified
in this European Standard.
The Plena Voice Alarm System uses the
following color coding for indications
throughout the system:
– Green: system ok
– Red: system/zone in voice alarm
condition
– Yellow: system in fault warning
condition