122 en | Plena Voice Alarm System
9922 141 1037x (V2.16) | V0.6 | 2011.09 Installation and Operation manual Bosch Security Systems B.V.
6 The quiescent condition
Clause / Requirement Compliance Signature
Any kind of system information may be
displayed during the quiescent condition.
However, no indications shall be given which
could be confused with indications used in the
Plena Voice Alarm System is compliant.
– voice alarm condition, If the Plena Voice Alarm System enters the
voice alarm condition, controller, remote
control panels (including fireman’s panel),
and each call station will show a red
system status LED. In the quiescent
condition no red indicators are used at all
and the display of the controller will never
automatically switch to the emergency
menu.
– fault warning condition, If the Plena Voice Alarm System enters the
fault warning condition each call station
will show a yellow fault LED. Yellow LEDs
are solely used for fault condition.
– disablement condition (option with
requirements).
The disablement condition is not
implemented in Plena Voice Alarm System.