130 en | Plena Voice Alarm System
9922 141 1037x (V2.16) | V0.6 | 2011.09 Installation and Operation manual Bosch Security Systems B.V.
8.2.6 Indication of faults related to the
transmission path to the CIE (option with
requirements)
The VACIE may have provision for an indication of
faults related to the transmission path to the CIE.
In this case, the short-circuit or interruption of
the transmission path to the CIE shall be
indicated by means of a separate light emitting
indicator and/or an alphanumeric display.
Plena Voice Alarm System is compliant.
All input contacts of the Plena Voice
Alarm System can be supervised for short
and interruption.
Open Interface connections are
supervised through keep-alive messaging.
Faults related to the transmission path to
the CIE are therefore individually
reported and can be inspected using the
front panel of the controller or the
logging application. The faults are also
reported through the general fault
warning indication.
8.2.7 Indication of faults related to voice alarm
zones (option with requirements)
The VACIE may have provision for an indication of
faults related to voice alarm zones. In this case
the short-circuit or interruption of a voice alarm
transmission path between the VACIE and the
loudspeakers in that zone shall be indicated by
means of a separate light emitting indicator per
zone and/or an alphanumeric display.
Plena Voice Alarm System is compliant.
Faults that occur in the Plena Voice Alarm
System are reported per defective zone
or monitored function.
8.3 System fault Plena Voice Alarm System is compliant.
A system fault is a fault as specified in 14.4
Program monitoring (see also Annex C)or 14.6
Monitoring of memory contents in the case of
software controlled VACIE. A system fault may
prevent requirements of this European Standard,
other than those specified below, from being
fulfilled. In the event of a system fault at least the
following shall apply:
a a system fault shall be visibly indicated by
means of the general fault warning indicator
and a separate light emitting indicator on the
VACIE. These indications shall not be
suppressed by any other functional condition
of the VACIE and shall remain until a manual
reset and/or another manual operation at
access level 2 or 3;
System faults are individually reported by
the Plena Voice Alarm System and can be
inspected using the front panel menu of
the controller or the logging application.
Faults are also reported through a
general fault warning indicator,
connected to a control output.
Both the individual fault indicator of each
system fault and the general fault
warning indicator are not suppressed by
any other functional condition of the
Plena Voice Alarm System.
Clause / Requirement Compliance Signature