132 en | Plena Voice Alarm System
9922 141 1037x (V2.16) | V0.6 | 2011.09 Installation and Operation manual Bosch Security Systems B.V.
8.5.2 Following reset, the indication of the
correct functional conditions corresponding to
any received signals shall either remain or be re-
established within 20 s.
If fault reset is performed while it is not
actually resolved in If faults are reset, all
individual faults that are not actually
resolved in the system are reported again
within 20 seconds. The sounder will not
resound. the system checks reported
fault first immediately. If the faults are
resolved when the reset is done, and the
fault reappear shortly afterward the
sounder will resound.
8.6 Transmission of the fault warning
condition
Plena Voice Alarm System is compliant.
The VACIE shall have provision for transmitting,
by means of at least general fault signal, all faults
specified in 8. This fault signal shall also be given
if the VACIE is de-energized.
The Plena Voice Alarm System controller
has a fixed fault output. This relay output
contact indicates no fault when open
(energized) and indicates a fault when
closed (de-energized). If the Plena Voice
Alarm System is de-energized this output
contact is closed, therefore the fault
signal will also be given.
Clause / Requirement Compliance Signature