ctrlX SAFETY | Device type SAFEX-C.12 51/83
DOK-XSAFE*-SAFEX-C.1XC-IT03-EN-P, Edition 03, Bosch Rexroth AG
Tabelle 34: LED Ethernet 1-LINK / LAN
LINK / LAN
Ethernet
Color Flashing pattern Meaning
- Off No connection
Green Permanently illuminated A connection to the network is
available
Yellow Flashing
A connection to the network is
available with telegram traffic
(Ethernet communication active)
L/A
EtherCAT
Color Flashing pattern Meaning
Yellow Off No link to EtherCAT master is
available
Yellow On Link to EtherCAT master is
available, no activity on the bus
Yellow Flashing
Link to EtherCAT master is available
with active data transmission
EtherCAT - Diagnostics
Tabelle 35: LED Ethernet 1 status - EtherCAT, combination of RUN and Error LED
Fieldbus status
(NET ST)
Color Flashing pattern Meaning
- Off Initialization
Green Flashing PRE-OPERATIONAL
Green Flashes once SAFE-OPERATIONAL
Green Permanently
illuminated
OPERATIONAL
Red Off No error
Red Flashing Invalid configuration
Red Flashes once Local error
Red Flashes twice Watchdog timeout