5-4 Instructions for Use Rexroth EcoDrive 03 DKC**.3-016
DOK-ECODR3-DKC16*UL***-IB01-EN-P
Note:
• Exceeding allowed control voltage generates error
message "+24 volt error". (=> See also functional firmware
description.)
• Control voltage failure causes the running motor to coast
torque-free (without brake).
DANGER
Dangerous movements due to unbraked
coasting of motor with control voltage failure!
⇒
Personnel should not remain within the area of the
machine with moving parts. Possible preventive
steps against unauthorized access are:
– protective fencing
– bars
– covers
– light barriers
⇒
The fences must be able to withstand the maximum
possible force that the machine can generate.
Drive halt (AH) and Drive enable (RF)
Note:
• Inputs work with inactive bus communication.
• Inputs don't work with active bus communication (SERCOS
interface, Profibus-DP, ...).
AP5393f1.FH7
X1
2
5
1
AH
3
RF
4
6
drive halt
drive enable
device-external device-internal
Fig. 5-7: Connections for drive halt and drive enable
R1 R3
R2
C1
I
n
Ap5183f1.fh7
Schematics
R1: 10k
R2: 3k3
R3: 10k
C1: no data
Fig. 5-8: Input circuit
Connection
AH and RF:
Input circuit
AH and RF: