Rexroth EcoDrive 03 DKC**.3-016 Ratings and Dimensions 3-1
DOK-ECODR3-DKC16*UL***-IB01-EN-P
3 Ratings and Dimensions
Description Symbol Unit DKC**.3-016
listing according UL-standard (UL) UL 508 C
listing according CSA-standard (UL)
Canadian National Standard(s) C22.2
No. 14-05
UL files (UL) E134201
pollution degree (UL)
Use in a pollution degree 2
environment
maximum ambient temperature with nominal data (UL) T
amax
°C 45
maximum ambient temperature with reduced nominal
data (UL)
T
amax_red
°C 55
Weight m kg 3.2
Device height (UL)
1)
H mm 287
Device depth (UL)
2)
T mm 229
Device width (UL)
3)
Bmm 65
minimum distance on the top of the device
4)
d
top
mm 150
minimum distance on the bottom of the device
5)
d
bot
mm 80
rated control voltage input (UL)
6)
U
N3
V 24 (±5%)
rated power consumption control voltage input without
holding brake, without control section at
U
N3
= DC 24 V (UL)
7)
P
N3
W17
short circuit current rating, SCCR, symmetrical
amperes (UL)
8)
I
SCCR
A rms 42000
rated input voltage, power (UL)
9)
V 200 … 480
tolerance rated input voltage (UL) % ±10
input number of phases (UL) 1 × AC, 3 × AC
input frequency (UL) f
LN
Hz 50 … 60
tolerance input frequency (UL) % ±2
maximum input current (UL)
10)
I
L_cont
A1.7
branch circuit protection fuse (UL)
11)
2
field wiring material (UL)
12)
Use 60/75 °C copper wire only, use
class 1 wire only or equivalent
required wire size according UL 508 A (internal wiring);
at I
L_cont
(UL)
13)
A
LN
AWG 16
maximum output voltage (UL) U
out
V 800
output number of phases (UL) 3
maximum output current (UL) I
out_max
A16
maximum output frequency (UL) f
out
Hz 1000